Calculate load end currents.
Load per phase= 1320kW/3 = 440kW
Current magnitude = 440/ { (0.415/sqrt(3) ) x 0.74} = 2481.5A
θ= cos -1 0.74 = 42.3°
IR= 2481.5 /_-42.3° A
Since loads are balanced,
IY=2481.5 /_(-42.3-120) ° A = 2481.5 /_-162.3° A
IB = 2481.5 /_(-42.3-240) ° A = 2481.5 /_-282.3° A.
Since load current is 2481.5 A, use 3000A 43kA TPN busbar.
Given line voltage is 415 V.
Let VRn be the reference phasor ,VRn= (415 /1.732) /_0°= 240/_ 0° V
VYn= (415 /1.732) /_0°= 240/_ -120° V
VBn= (415 /1.732) /_0°= 240/_ -240 ° V
VRY= 415/_ 30° V .........Note: Why 30° ? Textbook says so !
VYB= 415/_ (30-120)° = 415 /_ -90° V
VBR= 415 /_ (30-240)° = 415/_ -210° V
Calculate power factor correction capacitor:
Take, for example, max load demand (MD) of Main Switchboard (normal supply) of 1320kW
Assume power factor is to be corrected from expected low value, pfi =0.74 to final power factor pff=0.85
Using basic trigonometry as shown in Power Diagram above, required reactive power to compensate low power factor of 0.74 to 0.85 can be easily obtained as:
y =1320 x tan 31.8o=818kVar
(x + y) = 1320 x tan 42.3o = 1200kVar
Therefore x = 1200 - 818= 382 kVar capacitors have to be installed.
A 6-step or 12-step PF regulator is used to control amount of reactive load to be connected in parallel between incomer supply line and load end.
Reactive load per phase = 1/3 x 382 kVar = 127.3 kVar
3-phase currents to delta-connected
capacitors = 382 kVar /(1.732 x 415V) =531A.
Let's prove it
Let's prove it
Calculate phase current in capacitor
circuits.
IRY= (SRY/VRY)* =
[127.3 /_-90° kVar/415/_30° V ] *= 306.7/_ 120° A
IYB= (SYB/VYB)* =
[ 127.3/_-90° kVar/ 415/_ -90° V ] *= 306.7/_0° A
IBR= (SBR/VBR)* =
[ 127.3/_-90°kVar/ 415/_ -210° V] *= 306.7/_-120°
Note: * denotes
conjugate.
Calculate line currents to cap
banks.
IRd = IRY -
IBR = 306.7/_ 120 - 306.7/_-120 = 531/_90°
IYd= IY B- IRY =306.7/_0
- 306.7/_120°= 531/_ -30°
IBd=IBR -
IYB= 306.7/_-120 - 306.7/_0 =531/_ -150°
It's proven that line currents to
delta-connected capacitors is 531A.
Suggest to use 600A 4-pole MCCB
From Table 4D1A of Wiring
Regulations (BS7671-17th Edition),
Cable size , therefore, must have
capacity of > 600 A
Try use 2 nos 240 mm sq PVC cables
per phase = 346 A x 2= 692A per phase > ACB size of 600A. (OK!)
Therefore for the 3-phase incoming
supply, use 8 x 1core 240 mm sq PVC cables in trunking.
Calculate supply currents.
IR,sum = IR + IRd = 2481.5 /_-42.3° + 531/_90° = 1835.4 -j1139.1 = 2160 /_31.8°
IY,sum = IY + IYd = 2481.5 /_-162.3° + 531/_ -30° = 1904.2 -j1020.0 = 2160 /_28.2°A
IB,sum = IB + IBd = 2481.5 /_-282.3° + 531/_ -150° = 68.7 + j2159 = 2160/_88.2°A
When adding capacitors close to loads end, we see a saving in current consumption. Instead of supplying 2481.5A to loads, only 2160A supply current is required !
No comments:
Post a Comment