Saturday, 19 September 2015

Overview of Voltage & current - magnitude & phase angle


Always set Voltage (red phase to neutral) as reference phasor.ie Vrn= |Vrn|/_0°

The next Voltage drawn in clockwise rotation (yellow phase to neutral, Vyn) is displaced by 120° with respect to reference phasor. So Vyn= |Vyn|/_120°

The next Voltage again drawn in clockwise rotation after Vyn is (blue phase to neutral, Vbn) displaced by 240° with respect to reference phasor. So Vbn= |Vbn|/_240°

Let's start calculating load currents.

Assume a balanced 3-phase load of 900kW is delivered from 415Vac 3-phase source at power factor 0.8 lagging.

Load per phase = 900kW/3 =300kW

3-phase current magnitude = 900kW / (√3 x 0.415 kV x 0.8) = 1565 A

Load current always lags it's phase Voltage by an angle of cos -1pf where pf is power factor.

Angle = cos -1pf = cos -1 0.8 = 36.9 °

Phase current IR= 1565 /_-36.9° A. The -ve sign shows that the current IR lags phase Voltage |Vrn|/_0° by 36.9 °




Email: sobisal@gmail.com

No comments:

Post a Comment